E&P-02 Controller, digital type electro-pneumatic controller is designed to control
Process variables such as pressure, temperature, liquid level and so on.
It provides All the latest digital electronic control functions with reliability & precision of a pneumatic Controller.
Controller is composed of several major parts including Digital Signal Processor, flash ROM for program/data
storage, analog-digital signal filter, WatchDog circuits, RS232/485 Communication interface & a pair of solenoid
valves and etc..
The algorithm for PID control & auto-tuning was adopted as control software.
Electro-Pneumatic Controller operates that It accepts the signals standard 4~20mA and/or Pt100 from a sensor
(transmitter), and CPU forward output signal,
To be calculated by PID. It¡¯ll provides Pneumatic output to operate diaphragm or piston actuated control valves.
Because of this feature E&P-02 doesn¡¯t use I/P transducer and/or valve Positioner, it operates actuator directly
thus reducing the costs.

¡Ü FEATURE
1) Micom controller that apply the newest technology
2) It is FND Display type which is easy to check and good for temperature character.
3) P, PI, PID, Auto-Turing faculty.
4) Supply to insert direct current 24voltage for Transmitter.
5) Display process Progress Value(PV), Setting Value(SV), Deviation Value(DEV), Min /Max, Unit etc.
6) Built in remote monitoring faculty.
7) Simple design and economic.
8) Various input to RTC, Transmitter, Thermocouple.
9) Quality guaranteed to achieved CE_EMC

¡Ü Specification
Model E&P-01 E&P-02
Supply Voltage 110/20VAC,50/60Hz,24V DC 110/220VAC,50/60Hz,24V DC
Operating Voltage Range 90~110% of Rated Voltage 90~110% of Rated Voltage
Power Consumption 10W(MAX.) 6W(Steady State) 10W(MAX.) 6W(Steady State)
Input Signal 4~20mA,PT100ohm,K,(1~5V) 4~20mA,PT100ohm,K,(1~5V)
Output Signal DC4~20mA AIR1.4~2.4K
Control Action DIRECT or REVERSE DIRECT or REVERSE
Accuracy +/-0.3% of Full Span +/-0.3% of Full Span
Control Functions PID Control Functions, Auto-Tuning PID Control Functions, Auto-Tuning
Alarm Output Relay Contact Output(A) Relay Contact Output(A)
  Error LED Lamp Error LED Lamp
Local Set Point Adjustment UP/DOWN Push Button UP/DOWN Push Button
Display LED,FND Display LED,FND Display
Adjustable Parameters SV,PV,PID,Unit SV,PV,PID,Unit
Self-Diagnostic Watch-Dog Circuit Watch-Dog Circuit
Communication(Optional) RS232 or RS485(Option) RS232 or RS485(Option)